Data center

Hamburg, Germany

Colocation at Artfiles W408 – redundant power supply, biometric access, and cold-aisle cooling for up to 5 kW per rack. Your hardware in a professional data center environment.

Key figures

550 m²
Total area
120
Racks (19")
5 kW
per rack
100 %
Green power

What sets this site apart

  • Biometric access

    Hand-vein scanner, badge & PIN – multi-stage access from the premises to colocation.

  • UPS + emergency power

    n+1 UPS, 10 min. bridging time, 690 kVA diesel – pre-heated around the clock.

  • Cold aisle & cooling

    Rittal racks, cold-aisle containment, up to 240 kW cooling capacity (n+1).

General information

Year built
2011 (completion)
Location
Wendenstraße 408, 20537 Hamburg
Total area
approx. 550 m²
Colocation area
Two fully separate fire compartments, each approx. 225 m²
Capacity
Space for around 120 cabinets (19" racks), distributed across both fire compartments
Build-out status
Site fully built out since 2016

Rack and climate concept

Rack system
Racks from Rittal
Airflow
Cold-aisle containment for even supply-air distribution to the racks
Climate concept
Designed for high power density per rack; air conditioning and UPS configured redundantly (n+1)

Security

Site access
Rolling gate, with access card (badge)
Building access
With access card (badge) and PIN
Colocation access
Biometric authentication (e.g. hand-vein scanner)
Intrusion protection
24/7 security service, motion detectors, alarm system, comprehensive video recording in colocation. Combination locks on racks.
Fire protection
Early fire detection system and Inergen gas suppression system
Building monitoring
In addition to smoke detectors, floor moisture sensors and cold-aisle air pressure monitoring — for early detection of anomalies and rapid response

Power supply

Transformer station
Own conversion 10 kV → 400 V; expansion space reserved for downstream infrastructure
Grid connection
Four main tracks with three phases each — separate main lines and protection down to the racks for a high level of redundancy
Power design per rack
Area designed to provide approx. 5,000 W electrical power per rack and dissipate the associated heat (cooling)
UPS
Socomec Masterys GP (quantity: n+1), each 120 kVA at full load
Bridging time
10 minutes guaranteed at maximum load
Emergency generator
Aggretech AGS670V_E53 with 690 kVA at full load
Start-up time
The pre-heated generator typically reaches full output within about one minute (start-up phase secured by UPS)

Cooling

Air conditioning type
Stulz Cyberair 2 and Cyberair 3
Cooling capacity
Approx. 80 kW per cabinet, currently up to 240 kW cooling capacity at full load (redundant n+1 design)
Air volume
Up to 20,000 m³/h (per cabinet), differential-pressure controlled.

Sustainability

Power supply
Operation with 100% electricity from renewable sources (provably allocated generation — details on request)

Insights into colocation, cold aisles, and on-site infrastructure.

6 photos
  • Artfiles W408 data center
  • Artfiles W408 data center
  • Artfiles W408 data center
  • Artfiles W408 data center
  • Artfiles W408 data center
  • Artfiles W408 data center

Network & connectivity

100G Lumen, 100G Zayo, DE-CIX, Deutsche Telekom, and Path Network DDoS protection – all from one location in Hamburg.

Go to connectivity overview

Back to homepage